(1) Application
DEP-800 series are used for 6 ~ 110KV power systems
with insulated, resistance earthed or impedance earthed
neutral. Optional to be installed standalone or on switchgear
cubicles.
(2)
Product Features
Integrated with protections, monitoring and control
functions in one assembly, instead of being separated.
Reduced wiring brings stronger anti-interference capability.
All the assemblies are connected via LonWork field network.
The single-wire diagram and digital states can be displayed
on the liquid crystal screen in the assembly.
Adaptive to 0.5 ~ 5A tripping and closing current eliminates
the requirement for the user to provide breaker parameters.
Distributed power supply reduces the consumption of
energy to 8 W or less.
Wider range of working ambient temperature reinforces
reliability. The built-in RTDs can provide over-temperature
or under-temperature alarming if necessary.
Fault recording function extends its capability.
(3) Main Monitoring and Control Functions
I,V,P,Q,COSΦ,f,KWH can be calculated from analog inputs
by 3-phase PT/CTs.
8 digital inputs from external physical contacts, 8
digital indications from internal logical protection
states.
2 pulse inputs can be accumulated.
1 digital output works as control command.
Event recording and SOE.
To communicate with local systems via LonWorks field
bus.
(4) Main Protection Functions
Microprocessor Based Feeder Protective Relay with Monitoring
and Control Function (DEP-821)
*3-stage definite-time low-voltage-blocked overcurrent
protection
*Inverse-time overcurrent protection ( IEC/ANSI 3 characteristics
optional )
*Pre-acceleration, post-acceleration, and manual switch-on
acceleration
*3-pole 3-shot non-check auto reclosure
*Distributed low-frequency load shedding
*Zero-sequence overcurrent protection and earthed-phase
selection
*Overload protection
*Fault recording and data logger
Microprocessor Based Line Protective Relay with Monitoring
and Control Function (DEP-822)
*3-stage complex-voltage blocked directional overcurrent
protection
*Inverse-time overcurrent protection ( IEC/ANSI 3 characteristics
optional )
*Pre-acceleration, post-acceleration, and manual switch-on
acceleration
*3-pole 3-shot auto reclosure ( non-check, synchronization
check, non-voltage check optional)
*Distributed low-frequency load shedding
*Zero-sequence overcurrent protection and earthed-phase
selection
*Overload protection
*Fault recording and data logger
Microprocessor Based Capacitor Bank Protective Relay
with Monitoring and Control Function (DEP-825)
*3-stage overcurrent protection
*Inverse-time overcurrent protection ( IEC/ANSI 3 characteristics
optional )
*Over-voltage protection
*Low-voltage protection
*Zero-sequence overcurrent protection and earthed-phase
selection
*Differential currents and differential voltages protection
*Fault recording and data logger
Microprocessor Based Auto Backup Switch-on and Sectionalizer
Protective Relay with Monitoring and Control Function
(DEP-827)
* Back-up incoming line auto switch-on
*Back-up segregator auto switch-on
*Short-time open overload co-shedding
*Segregator protection: energizing protection, complex-voltage
blocked overcurrent protection, inverse-time overcurrent
protection, post-acceleration, zero-sequence overcurrent
protection
*Fault recording and data logger
Microprocessor Based Motor Protective Relay with Monitoring
and Control Function (DEP-829)
*Overcurrent protection and locked/stalled rotor protection
*Inverse-time overcurrent protection ( IEC/ANSI 3 characteristics
optional )
*Negative sequence overcurrent protection
*Pilot-wire differential protection
*Zero-sequence overcurrent protection and earthed-phase
selection
*Low-voltage protection
*Over load alarming
*Fault recording and data logger
(5) Specification
(a) Current/voltage Setting error : <2%
Frequency setting error : <0.01HZ
Time setting error for definite time: <50ms
Time setting error for inverse time: <2 s
(b) Measurement accuracy and resolution
Current/voltage: 0.2%
Active power/reactive power: 0.5%
Power factor: 0.5%
SOE resolution: ≤2ms
Pulse input resolution: ≤2ms
Analog input refresh rate: <2s
(c) Working temperature: -25oC ~ +60oC
(d) Dielectric test voltage: 2 KV/AC, 1 min.
Surge test voltage: 5KV
(e) Mechanical stress tests, vibration, shock stress
and seismic vibration
IEC60255-21-1, Class II
IEC60068-2-6
(f) EMC tests
IEC60255-22-1 HF Disturbance Test with Damped Oscillatory
Wave, Class III (2.5KV c.m. 1KV d.m.)
IEC60255-22-2 Electrostatic Discharge Disturbance Tests,
Level IV
IEC60255-22-3 Radiated Electromagnetic Field Disturbance
Tests, Class III
IEC60255-22-4 Fast Transient Disturbance Tests, Class
III
|