(1) Application
DEP-500 is used for two-winding or three-winding transformers
of 110KV or below voltage levels.
(2) Functions
(a) DEP-531 Differential Protection Relay for Transformers
DEP-531 is used as differential protection for transformers
of 110KV or below voltage levels. Its main functions
are: differential overcurrent time protection, ratio
differential protection, blocking when CT wiring broken
(b) DEP-535 Backup Protection for Transformers
DEP-535 is used as backup protection for transformers
of 110KV or below voltage levels. It is designed in
max. mode, e.g., it can be used for high voltage side,
medium voltage side, or low voltage side, the corresponding
protection function can be selected by different control
word.
Main functions: 3-stage complex-voltage blocked overcurrent
protection, 3-stage zero-sequence overcurrent protection,
clearance discharging zero-sequence overcurrent protection,
zero-sequence overvoltage protection, overvoltage alarming,
overload alarming, fan start/stop, tap changer blocking,
PT wire broken blocking and alarming, etc.
(c) DEP-539 Non-electrical Protection for Transformers
DEP-539 is used for non-electrical protection of transformers.
It has 10 non-electrical restart relays and up to 4
independent operation circuits. It is designed to protect
all the non-electrical objects of transformers and the
operation circuits in each side of transformers.
(d) DEP-550 communication controller
DEP-550 communication controller is used for manage
all the communications among different protection relays.
It supervises all the protection relay units, transmits
all the messages to master stations or local SCADA system,
receives commands from master stations or local SCADA,
and exchange data with other intelligent electronic
devices.

(3) Specification
(a) Ratings
DC voltage - 220V/110V, ±15%
AC voltage - 100V/57.7V
AC current - 5A/1A
Rated frequency - 50HZ
(b) Setting errors
Current/voltage setting error -<5%
Time setting error -- <1% or 50 ms
(c) Environmental Requirements
Working temperature -- -10 oC ~ +60 oC
Storage temperature -- -30 oC ~ +70 oC
Relative humidity - ≤ 95%
Pressure - 86 ~ 108 kpa
(d) EMC Tests
IEC60255-22-1 HF Disturbance Test with Damped Oscillatory
Wave, Class III (2.5KV c.m. 1KV d.m.)
IEC60255-22-2 Electrostatic Discharge Disturbance Tests,
Level IV
IEC60255-22-4 Fast Transient Disturbance Tests, Class
III
(e) Mechanical Stress Tests, Vibration, Shock Stress
and Seismic Vibration
IEC60255-21-1
(f) Overload Resistance
AC current loop: 2 times of rated current, able to continue
working without any limit
10 times of rated current, able to continue working
for 16 hours
40 times of rated current, able to continue working
for 1 hour
AC voltage loop: 1.2 times of rated voltage, able to
continue working without any limit
(g) Output contacts
Max. capacity of the output contacts is 150 W/1250w,
max. working current is 5 A, but arc extinction is not
permitted.

(4) Mechanical data and installation
Standard 4 U chassis, installed in cabinet
|